Kingsine Electric Automation Co., Ltd.

Kingsine Electric Automation Co., Ltd. Specialize in Electric Power Testing

Manufacturer from China
Verified Supplier
17 Years
Home / Products / Multifunctional Power Meter /

MODBUS-RTU Protocol Multifunctional Power Meter

Contact Now
Kingsine Electric Automation Co., Ltd.
Visit Website
City:shenzhen
Province/State:guangdong
Contact Person:MissAmy
Contact Now

MODBUS-RTU Protocol Multifunctional Power Meter

Ask Latest Price
Video Channel
Place of Origin :China
Brand Name :Kingsine
Certification :ISO9001,CE
Model Number :PMC100N
MOQ :1PC
Delivery Time :15 working days
Payment Terms :T/T in advance ,L/C
Supply Ability :5000PCS/Month
Contact Now

Add to Cart

Find Similar Videos
View Product Description

MODBUS-RTU Protocol Multifunctional Power Meter

single phase electric parameter measurment and energy metering

On-line monitoring of electric parameter limit alarm

Network meter without LCD operation panel, optional transducer function output

Support MODBUS-RTU, RS485 communication


Overview


PMC100N single phase network power meter is a multifunctional network meter without LCD operation panel. It adopts low power dissipation microprocessor, can measuring complete power parameter, energy measurement. It has RS-485 communication port and could be easily integrated to any intelligent power distribution system. PMC180N has the practical function, easy use, easy maintenance. It can use to monitor and control of the on-site equipment, supply the measuring & testing support to the power application specialist, supply the data base to the SCADA and Smart Grid, provide scientific basis for intelligent energy management.

Function Features

Function Features

PMC100Z

PMC100C

PMC100P

PMC100F

PMC100U

PMC100I

PMC100N

Instantaneous real virtual value

current

voltage

frequency

active power

reactive power

power factor

Energy

active energy

Communication

RS485 /MODBUS protocol

Display

LED display

other

2 channel DI

2 channel DO

1 channel AO :4-20mA

2 channel limits alarm

support program online upgrade

Technical parameter

Electrical Characteristics

Measurement Type

single phase AC system

Sampling rate per cycle: 64 times

Data refresh rate

1S

Measurement Accuracy

Current

0.2%

Voltage

0.2%

Power

0.5%

Frequency

0.05Hz

Active Energy

1.0%

Input voltage characteristics

Measuring voltage

0~600 V (Direct Access)

Allowed overload

1.2 times / continuous

Input impedance

1.8MΩ

Input current characteristic

Measuring current

5A or 1A (Via CT Connect)

Allowed overload

1.2 times / continuous

Input impedance

<0.1Ω

Binary input

Working voltage

12~24 VDC external power supply)

Input impedance

12KΩ

Isolation voltage

2KV

Relay output

Node Type

Mechanical shock

Node capacity

220 VAC/5A, 30 VDC/5A

4-20mA AC input

Open circuit voltage

5VDC

overload capacity

≤200Ω

Isolation voltage

2KV

AC

85~265 VAC/45-65Hz

DC

100~300 VDC

Power dissipation

< 2.5W

Mechanical properties

Weight

0.3kg

IP protection grade

IP52

Size

75 X 55 X120 mm

Operating temperature

-25~70℃

Storage Temperature

-40~85℃

Relative Humidity

5% - 90%RH, No condensation

EMC

Electrostatic discharge interference

IEC 61000-4-2, Level 4

Group of anti-fast transient pulse

IEC 61000-4-4, Level 4

Anti-impact

IEC 61000-4-5, Level 3

Anti-frequency magnetic field

IEC 61000-4-8, Level 3

Electrical insulation performance

Insulation resistance

GB/T13729, >50MΩ

Frequency withstand voltage

GB/T13729, AC 2KV 50Hz /1min

Impulse voltage

GB/T13729, 5KV, 1.2/50us

Inquiry Cart 0