Kingsine Electric Automation Co., Ltd.

Kingsine Electric Automation Co., Ltd. Specialize in Electric Power Testing

Manufacturer from China
Verified Supplier
17 Years
Home / Products / CT Analyzer /

Current Transformer Test Set IEC60044-1 CT Analyzer KT210

Contact Now
Kingsine Electric Automation Co., Ltd.
Visit Website
City:shenzhen
Province/State:guangdong
Contact Person:MissAmy
Contact Now

Current Transformer Test Set IEC60044-1 CT Analyzer KT210

Ask Latest Price
Brand Name :Kingsine
Model Number :KT210
Certification :CE/ISO9001
Place of Origin :China
MOQ :1 set
Price :Negotiation
Payment Terms :L/C,T/T
Supply Ability :100 sets/month
Delivery Time :15 working days
Voltage Range :0~300V
Voltage Accuracy :±0.1%
Size (W x H x D) :360 x 140 x 325mm
Weight :<8 kg (without accessories)
Operating Temperature :-10°C up to + 55°C
Humidity :Relative humidity 5% up to 95% not condensing
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

Current Transformer Test Set IEC60044-1 CT Analyzer KT210

Description Of Current Transformer Analyzer

Complete measurement function, it can test all type current transformer for secondary overload, secondary loop resistance, excitation characteristic, transient characteristic, ratio difference, angle difference and polarity. It can also test exact limit coefficient(ALF), device security coefficient(FS), secondary time constant(Ts), remanence coefficient(Kr), transient area coefficient(Ktd), inflexion voltage, current, level, saturation inductance, un-saturation inductance, 5% 10% error curve, of current transformer, hysteresis loop for current transformer, and evaluate test result according to defined standard.

Feature Of Current Transformer Test Set

High measurement accuracy, resistance accuracy is 0.1%+1mΩ, phase accuracy±0.05 degree, variable accuracy is ±0.1% (1-5000 ), variable accuracy is ±0.2%(5000-10000).
It can test current transformer according to IEC60044-1, IEC60044-6, IEC61869-2 and ANSI30/45 standard etc.
Complete measurement function, it can test all type current transformer for secondary overload, secondary loop resistance, excitation characteristic, transient characteristic, ratio difference, angle difference and polarity. It can also test exact limit coefficient(ALF), device security coefficient(FS), secondary time constant(Ts), remanence coefficient(Kr), transient area coefficient(Ktd), inflexion voltage, current, level, saturation inductance, un-saturation inductance, 5% 10% error curve, of current transformer, hysteresis loop for current transformer, and evaluate test result according to defined standard.
PT Test As for those inductive PT based on the definition of GB1207-2006(IEC60044-2), KT210 CT/PT Analyzer can also test them. KT210 CT/PT Analyzer can do variable ratio, polarity and secondary winding excitation test of inductive PT.

Specification Of Current Transformer Test Device

Voltage Measurement Input
Secondary Input Range 0~300V
Max Knee point 30KV
Secondary Input Accuracy ±0.1%
Primary Input Range 0~30V
Primary Input Accuracy ±0.1%
Output
Output Voltage 0 Vac to 120 Vac
Output Current 0 A to 5 A (15 A peak)
Output Power 0 VA to 450 VA (1500 VA peak)
Main Power Supply
Input Voltage 176 Vac to 264 Vac @ 10A Max
Permissible Input Voltage 120 Vdc to 370 Vdc @ 5A Max
Frequency 50 / 60 Hz
Permissible Frequency 47 Hz to 63 Hz
Connection Standard AC socket 60320
Physical Dimensions
Size (W x H x D) 360 x 140 x 325mm
Weight <8 kg (without accessories)
Environment Conditions
Operating Temperature -10°C up to + 55°C
Storage Temperature -25°C up to + 70°C
Humidity Relative humidity 5% up to 95% not condensing

Advantage Of Current Transformer Test System

Easy to operate CT / PT Analyzer,
120V / 15A Current Output,
9.7 inch touch screen operation,
IEC60044-1, IEC60044-6, IEC61869-2, ANSI30/45 standard
High stability for bushing CT testing;

FAQ

Q: Can the device test the function of Synchronising or synchronism-check relays?

A: Yes.

Q: How about the guarantee of repair?

A: All of our products have 3-years guarantee of free repair, and life-long maintenance.

Q: What is your technical advantages?

A: Easy to operate, measure quickly, all test can be done automatically based on the same connection line type except overload impedance measurement.

Inquiry Cart 0